TAD1351GE, TAD1352GE, TAD1353GE,
TAD1354GE, TAD1355GE
Parameter Alarm Engine protection
Setting range Default setting Derating level Action
Oil temperature 120-130 °C
(248-266 °F)
125 °C
(257 °F)
Setting +5 °C
(9 °F)
Shutdown
Oil pressure Low idle - 150 kPa
(21.8 psi)
120 kPa
(17.4 psi)
Shutdown
1500 rpm - 250 kPa
(36.3 psi)
220 kPa
(31.9 psi)
Shutdown
1800 rpm - 300 kPa
(43.5 psi)
270 kPa
(39.2 psi)
Shutdown
Oil level - Min level - -
Piston cooling pressure,
>1000 rpm
- 150 kPa
(21.8 psi)
150 kPa
(21.8 psi)
Shutdown
Coolant temperature 95-103 °C
(203-217.4 °F)
102 °C
(215.6 °F)
Setting +5 °C
(9 °F)
Shutdown
Coolant Level - On Low level Shutdown
Fuel feed pressure Low idle - 150 kPa
(21.8 psi)
- -
>1400 rpm - 300 kPa
(43.5 psi)
- -
Water in Fuel - High level - -
Crankcase Pressure - Increased pres-
sure
Increased pres-
sure
Shutdown
Air filter pressure droop - 5.0 kPa (0.7 psi) - -
Altitude, above sea - - - Automatic derating
Intake manifold temperature - 80 °C
(176 °F)
85 °C
(185 °F)
Shutdown
Air inlet pressure - 310 kPa
(45.0 psi)
320 kPa
(46.4 psi)
Shutdown
Engine Speed 100-120 % of
rated speed
120 % of rated
speed
Alarm level Shutdown
Engine protection can be disabled. For consequences, see VP International Limited Warranty Policy.