Group 23 EMS 2 Limit values
21
Limit values
Limit values, control module (EMS 2) TAD1640–1642GE, TWD1643GE
Oil temperature
NOTE: The engine protection can be turned off.
Preset alarm limit Adjustable between Alarm lamp is lit Engine cut off
125 °C (257 °F) 120 - 130 °C at alarm limit +5 °C (+41 °F)
(248 - 266 °F)
Oil pressure
NOTE: The engine protection can be turned off.
Preset alarm limit Adjustable between Alarm lamp is lit Engine cut off
idle: 160 kPa (23,21 Psi) not adjustable at alarm limit 130 kPa (18,85 Psi)
1500 rpm: 250 kPa not adjustable at alarm limit 220 kPa (31,91 Psi)
(36,26 Psi)
1800 rpm: 300 kPa not adjustable at alarm limit 270 kPa (39,16 Psi)
(43,51 Psi)
Oil level
Preset alarm limit Adjustable between Alarm lamp is lit Engine cut off
low oil level not adjustable low oil level no
Coolant temperature
NOTE: The engine protection can be turned off.
Preset alarm limit Adjustable between Alarm lamp is lit Engine cut off
98 °C (208 °F) 95 -103 °C at alarm limit +5 °C (+41 °F)
(203 - 217,4 °F)
Coolant level
NOTE: The engine protection can be turned off.
Preset alarm limit Adjustable between Alarm lamp is lit Engine cut off
low coolant level not adjustable low coolant level low coolant level