Group 23 EMS 2 Limit values
24
Coolant level
NOTE: The engine protection can be turned off.
Preset alarm limit Adjustable between Alarm lamp is lit Torque limitation Engine cut off
low coolant level not adjustable low coolant level no no
Fuel pressure
Preset alarm limit Adjustable between Alarm lamp is lit Torque limitation Engine cut off
See diagram, fuel not adjustable at alarm limit no no
pressure below.
Water in fuel
Preset alarm limit Adjustable between Alarm lamp is lit Torque limitation Engine cut off
water in fuel not adjustable water in fuel no no
Crankcase pressure
NOTE: The engine protection can be turned off.
Preset alarm limit Adjustable between Alarm lamp is lit Torque limitation Engine cut off
increasing pressure not adjustable increasing no with increasing
pressure pressure
Fuel pres-
sure